Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Still deciding? Get samples of US$ 2900/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
3 Phase 380vac Three Phase Online UPS 20Kva 30Kva 40Kva 60Kva 80Kva 100Kva 120Kva 160Kva 200Kva
3 Phase 380vac Three Phase Online UPS 20Kva 30Kva 40Kva 60Kva 80Kva 100Kva 120Kva 160Kva 200Kva
3 Phase 380vac Three Phase Online UPS 20Kva 30Kva 40Kva 60Kva 80Kva 100Kva 120Kva 160Kva 200Kva
3 Phase 380vac Three Phase Online UPS 20Kva 30Kva 40Kva 60Kva 80Kva 100Kva 120Kva 160Kva 200Kva
Model | EH9500-60KVA/20 EH9500-90KVA/30 EH9500-120KVA/40 |
EH9500-100KVA/20 EH9500-150KVA/30 EH9500-200KVA/40 |
EH9500-200KVA/20 EH9500-300KVA/30 EH9500-400KVA/40 |
|
---|---|---|---|---|
Capacity | ||||
Module No. | RU-20/RU-30/RU-40 | RU-20/RU-30/RU-40 | RU-20/RU-30/RU-40 | |
Maximum Number of Modules | 3 | 5 | 10 | |
Input | ||||
Input | 3Ph+N+PE | |||
Rated Voltage | 380/400V/415Vac | |||
Voltage Range | 208~478Vac | |||
Frequency Range | 40~70Hz | |||
Power Factor | ≥0.99 | |||
Bypass Range | 80 upper limit:25%( +10% ; +15% ; +20% optional) 400 upper limit(20% ; +10% ; +15% optional) 415 upper limit(15% ; +10% optional) lower limit : -45% (-20%;-30% optional) Bypass frequency protection range: ±10% |
|||
Harmonic distortion(THDi) | ≤ 3% (100% non-linear load) | |||
Generator access | Support | |||
Output | ||||
Output | 3Ph+N+PE | |||
Rated Voltage | 380/400V/415Vac | |||
Power Factor | 0.9 | |||
Voltage Regulation | ±1% | |||
Output Frequency | AC Mode |
Synchronous with input; the maximum ±10% (±1%, ±2%, ±4%, ±5% can be set), |
||
Battery Mode | (50/60±0.2%)Hz | |||
Crest Factor | 3:1 | |||
Transfer Time | AC mode to bypass mode: 0ms (tracking); AC mode to battery mode: 0ms | |||
Overload Capability | Load≤ 110% for 60min, ≤ 125% for 10min, ≤ 150% for 1min, ≥ 150% turn to bypass mode immediately |
|||
Harmonic distortion(THDi) | ≤ 2%(100% Linear load) | |||
Others | ||||
Efficiency | Normal Mode 95% | |||
CommunicationInterface | RS232 RS485 2 Intelligent Slot (Smart card slot) dry connect | |||
Executive Standard | CE,EN/IEC 62040-2, EN/IEC 62040-1-1, YD/T1095-2008 | |||
Battery | ||||
Battery Voltage | ±192V±204V±216V±228V±240V DC; (32 pcs;34 pcs;36 pcs;38 pcs;40 pcs optional) |
|||
Charging Current | UPS Cabine | 30A Max. | 50A Max. | 100A Max. |
Power Module | 10A Max. | |||
Working Environment | ||||
Operating Temperature | 0ºC ~ 40ºC | |||
Relative Humidity | 0 ~ 95% non condensing | |||
Stored Temperature | -25ºC ~ 55ºC | |||
Altitude | < 1500m | |||
Physical Characteristics | ||||
Physical Dimension | Cabinet | 600 x 840 x 1400 | 600 x 1100 x 2000 | |
Module | 580 x 443 x131(3U) | |||
Net Weight (kg) | Cabinet | 157 | 169 | 306 |
Module | 33 |